1Logix 510si Digital PositionerThis product meets the requirements ofADK041400E - 04.03
10WARNING: During the Quick-Cal operation the valvemay stroke unexpectedly. Notify proper personnelthat the valve will stroke, and make sure the valve
11indicating that it is waiting for the maximum signal tobe input to the positioner. Normally this will be 20mA, but if split range operation is req
12Logix 510si Status Condition CodesColors Identifier Indication and resolutionG - - - Any sequence starting with a Green light flashing first is a no
13Colors Identifier Indication and resolutionY - - - Any sequence starting with a yellow light indicates that the unit is in a special calibration or
14Troubleshooting Logix 510si Digital PositionersFailure Probable Cause Corrective actionNo LED is blinking 1. Current source below 3.6 mA 1. Verify c
1512 SPARE PART KITSItem No. Description Part-No.1 Cover Assembly YellowWhiteBlack2a PC Board Assembly H101140002b PC Board Assembly with analog fee
16All data subject to change without notice©04.2002 Flowserve Corporation. Flowserve and Kämmer are trademarks of Flowserve CorporationRegional Headqu
2Table of Content Page1 General Information ... 32 Unpacking ...
31 USING FLOWSERVE VALVES, ACTUATORSAND ACCESSORIES CORRECTLY1.1 UsingThe following instructions are designed to assist inunpacking, installing and pe
41.6 Spare partsUse only FLOWSERVE original spare parts.FLOWSERVE cannot accept responsibility for anydamages that occur from using spare parts orfast
5Shipping weights(incl. mounting kit)Linearity < ± 1,0%Resolution < 0,3%Repeatability < 0,5%Deadband < 0,5%Operating Temperature Standard
6Figure 1: Logix 510si Principle of Operation5 PRINCIPLE OF OPERATIONThe Logix 510si positioner is a digital positioner withvarious options. The posit
7Compliance Voltage (Figure 9)Output compliance voltage refers to the voltage limit the cur-rent source can provide. A current loop system consists of
8Electromagnetic CompatibilityThe Logix 510si digital positioner has been designedto operate correctly in electromagnetic (EM) fieldsfound in typical
9•On enables an automatic tuning feature that willautomatically determine the positioner gain set-tings every time a “Quick-Cal” is performed.The gain