Automax Valve Automation Systems
Installation, Operation and Maintenance Instructions
LMR0016-0 (AUTO-16) 11/01 Page 2 of 2
Maintenance Instructions
Trouble Shooting the APS2
Actuator will not cycle.
1. Check for proper orientation of APS2.
2. Check for pinched diaphragm.
3. Check for plugged exhaust port.
Air leaks through breather exhaust when actuator
is held open.
1. Check for pinched diaphragm.
2. Check for diaphragm wear. Diaphragm should be
flexible with no tears.
3. Increase supply air pressure.
Assembly
1. Hold upper housing (2) with actuator ports side
down. Place large o-ring (4) into o-ring groove of
lower housing.
2. Place diaphragm (3) into center of bore of lower
housing. (See exploded view for diaphragm
orientation.)
3. Aligning pin in upper housing (1), place upper
housing on lower housing.
4. Fasten housing together with M5–.8 x 25 mm
SHCS (6) from lower housing side.
5. Attach breather vent (8) to lower housing, using a
sealant.
6. Place small o-rings (5) into o-ring grooves of
lower housing.
7. Mount to actuator with M5–.8 x 35mm SHCS (7).
Disassembly
Disassembly is reverse of assembly.
Standard Components
Part # Description Materials Qty. P/N
1 Upper Housing Aluminum 1 M610064
2 Lower Housing Aluminum 1 M610063
3 Diaphragm Polyurethane 1
4 O-Ring Nitrile 1 106073
5 O-Ring Nitrile 2 105775
6 M5––.8 x 25mm SHCS Steel 2
7 M5—.8 x 35mm SHCS Steel 2 106075
8 Breather Vent Bronze 1 106200