Automax Logix 3200IQ Digital Positioner
Installation, Operation and Maintenance Instructions
Positioner Operation
The Logix 3200IQ positioner is an electric feedback
instrument. Figure 2 shows a Logix 3200IQ positioner
installed on a double-acting actuator.
The Logix 3200IQ receives power from the two-wire,
4-20 mA input signal. However, since this positioner
utilizes HART communications, two sources can be used
for the command signal: Analog and Digital. In Analog
source, the 4-20 mA signal is used for the command
source. In Digital source, the level of the input 4-20 mA
signal is ignored and a digital signal, sent via HART,
is used as the command source. The command source
selection can be accessed with SoftTools software, the
HART 275/375 communicator, or other host software.
The input signal in percent passes through a
characterization/limits modifier block. The positioner
no longer uses CAMs or other mechanical means to
characterize the output of the positioner. This function
is done in software, which allows for in-the-field
customer adjustment. The positioner has three basic
modes: Linear, Equal Percent (=%) and Custom
characterization. In Linear mode, the input signal is
passed straight through to the control algorithm in a
1:1 transfer. In Equal Percent (=%) mode, the input signal
is mapped to a standard 30:1 rangeability =% curve.
If Custom characterization is enabled, the input signal
is mapped to either a default =% output curve or a
custom, user-defined 21-point output curve. The custom
Figure 2: Logix 3200IQ Digital Positioner Schematic (air-to-open configuration)
Table VI: 4 to 20 mA Analog Output Specifications
Potential Range
40° to 95°
of Rotation
Power Supply Range 12.5 to 40 VDC, (24 VDC typical)
Maximum Load
(Supply voltage - 12.5) / 0.02
Resistance (ohms)
Current Signal Output 4-20 mA
Linearity 1.0% F.S.
Repeatability 0.25% F.S.
Hysteresis 1.0% F.S.
Operating Temperature
-40° to 176°F, -40° to 80°C
Table VII: Hazardous Area Certifications
FM/CSA
Intrinsically Safe Explosion Proof
Class I, Div 1, Groups A, B, C, D
Class I, Div 1,
Groups A, B, C, D
Class II, Div 1, Groups E, F, G
Class II, Div 1,
Groups E, F, G
(See Figure 2 for installation requirements.)
CENELEC
II 1G EEx ia IIC T4, T5
Intrinsically Safe T4 Ta = -40°C to 80°C
T5 Ta = -40°C to 35°C
Flameproof
II 2 GD EEx d IIB + H
2
T5, Ta = -40°C to 80°C
Compliant