Flowserve NRS 1-42 Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Matériel Flowserve NRS 1-42. Flowserve NRS 1-42 User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer

Résumé du contenu

Page 1 - NRS 1-42

1Installation Instructions 810373-03Level Switch Type NRS 1-42NRS 1-42

Page 2 - Contents

10UNITRONIC® is a registered trademark of LAPP Kabelwerke GmbH, StuttgartWiringInstallationNRS 1-42ToolInstallation on mounting rail1. Clip level swit

Page 3 - Wiring Diagram

11 Wire equipment in series. Star-type wiring is not permitted. Interlink screens of control cables such that electrical continuity isensured and conn

Page 4

12Node-IDCAN BusAll level and conductivity controllers and associated electrodes are interconnected bymeans of a CAN bus using the CANopen protocol. E

Page 5 - Parts Drawing

13Basic Adjustments – continued –Press button briefly.Sensitivity 0.5 µS/cm is selected.Press button briefly.Sensitivity range 1 (10 µS/cm,

Page 6

14OperationSwitchpoint 2Switchpoint 1Switchpoint 1 reached Time delay activated, LED 1 flashing Time delay elapsed, LED 1 permanently illuminated, rel

Page 7 - Important Notes

15AlarmThere are two alarm conditions: High-level (MAX) alarm Low-level (MIN) alarmLED 1 flashes rapidly.LED 1 remains permanently illuminatedafter

Page 8 - Explanatory Notes

16System MalfunctionsThere are four system malfunctions that might occur in the level switch and the levelelectrode: Max. admissible temperature in e

Page 9 - BUS FAULT”

17System Malfunctions – continued –The sources of malfunctions occurring in CAN bus systems operating with severalbus-based stations must be analysed

Page 10 - Installation

18System Malfunctions – continued –The terminal strip of the NRS 1-42 is live during operation.This presents the danger of electric shock.Cut off pow

Page 11 - Wiring – continued –

19LED “Bus status” flashes slowly.System Malfunction 4System Malfunctions – continued –Fault: Data transfer in CAN bus interrupted.Remedy:The bus cab

Page 12 - Basic Adjustments

2ContentsUsage for the intended purpose ...7Safety note ...

Page 13 - LEDs flash slowly

20System Malfunction 5LED flashes slowlySystem Malfunctions – continued –LED “Power” flashes slowly.Fault:The power supply unit (PSU) is overloaded.

Page 14 - Operation

21Fault finding list for troubleshootingThe terminal strip of the NRS 1-42 is live during operation.This presents the danger of electric shock.Cut off

Page 15 - Indicator LED 1 goes out

22If faults occur that are not listed above or cannot be corrected, please contact ourservice centre or authorized agency in your country.Malfunctions

Page 16 - System Malfunctions

23AnnexDangerThe terminal strip of the NRS 1-42 is live during operation.This presents the danger of electric shock.Cut off power supply before mounti

Page 17 - Check next system

24Annex – continued –OFFNode IDS11ONS22ONS34OFFS48OFFS516OFFS632ONS764OFFNode IDS11OFFS22ONS34OFFS48ONS516OFFS632OFFS7642070Fig. 8 (Factory setting)F

Page 18 - MAX/MIN alarm

25We hereby declare that the equipment NRS 1-42 conforms to the following Euopeanguidelines: LV guideline 73/23/eec version 93/68/eec EMC guideline 89

Page 19

26Terminal stripsSupporting rail 35 x 15 to DIN EN 50022KeyAC

Page 20 - – continued –

2710073118Example of InstallationFig. 11Fig. 1220 20

Page 21 - Malfunctions

28810373-02/304cm · © 2000 GESTRA GmbH · Bremen · Printed in GermanyGESTRA GmbHPostfach 10 54 60, D-28054 Bremen, Münchener Str. 77, D-28215 BremenT

Page 22 - Malfunctions – continued –

3Wiring DiagramFig. 2Fig. 1Twisted pair cableTwisted pair cable1) CEP = central earthing pointControl terminalURB 1Controller. . .Level electrodesNRG

Page 23 - Level electrode

4Wiring DiagramFig. 4Fig. 3Discharge control – Pump OFF at low levelTwisted pair cableTwisted pair cableFill control – Pump OFF at high levelTerminati

Page 24 - Fig. 9 (Example)

5Parts DrawingFig. 6Fig. 5AAB17 6 5 4 3 2

Page 25 - Annex – continued –

6Indicator LEDsLED 1 – switchpoint 1LED 2 – switchpoint 2LED 3 – switchpoint 3LED 4 – switchpoint 4LED “Bus status”LED “Power”Enter button / test mode

Page 26 - Terminal strips

7Important NotesSafety noteThe equipment must only be installed by qualified staff.Qualified staff are those persons who – through adequate training i

Page 27 - Example of Installation

8FunctionAt regular intervals the level electrode NRG 16-42 sends a data telegram to the levelswitch NRS 1-42. The data transfer is effected by means

Page 28 - GESTRA GmbH

9Technical dataType approval n°TÜV · WR 98-399Input/ OutputInterface for CAN bus to DIN ISO 11898 CANopenOutput – voltage supply for electrodePower su