Experience In MotionUSER INSTRUCTIONSMX/QX Profibus DP / PA Field UnitFCD LMENIM2336-03 – 12/12InstallationOperationMaintenance
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1210Figure 1.2 – Typical PROFIBUS PA Network with DCS or PLC as the Host
11PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comPROFIBUS Master SpecificationThe PROFIBUS master is the ne
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12122 System Components and Installation2.1 IntroductionThis section
13PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.com2.2 HardwareFigure 2.1a – MX-05 Actuator Figure 2.1b – Q
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12142.2.1 MX and QX ActuatorsThe MX and QX actuators are designed for op
15PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comFigure 2.3 – MX/QX PB PA Field UnitThe following commands
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12162.2.3.2 Token Rotation TimeThe time required for the rotation of the
17PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comThese distance rules (or limitations) are based on the ph
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1218Table 2.4 – Recommended PROFIBUS DP Cable TypesFC Standard Cable (Sie
19PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.com Figure 2.6 – Cable TopologiesPROFIBUSInterfaceNetworkDis
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/122Contents1 Introduction 51.1 Purpose 51.2 How to Use this Manual 51
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12202.2.5 Network Cabling for PROFIBUS PANetwork cabling should be in ac
21PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comTable 2.7 – Recommended Lengths of PROFIBUS PA Spurs (Stu
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12222.2.5.1 Cable Shielding and Grounding for PROFIBUS PAFor best perfor
23PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.com2.2.5.1 Cable Shielding and Grounding for PROFIBUS PAFor
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1224For cable connecting information on these components, refer to the fo
25PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.com• A safety ground, free of ground loop currents, running
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1226Figure 2.12(c) – PROFIBUS DP Cable Connections (Redundancy option wit
27PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.com• Shielded twisted-pair cables in compliance to PROFIBUS
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12283. Cut away the foil shield. Strip the insulation from the conductor
29PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comFigure 2.18 – Ring Tongue Connectors6. Connect the netwo
3PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.com5 How to Order Parts 55A Appendix – Wiring Diagrams 56
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1230Figure 2.19 – Connecting Network Cable to the MX/QX Terminal Block2.
31PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.com2.5 MX/QX PB Device SetupThe MX/QX PB option enables the
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12327. The unit will display PB ADDRESS 1–OK? If OK, select YES. If NO,
33PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.com1. Proceed through the Setup to the CHANGE PB/PA? displa
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12342.6 MX/QX PB Device Description, Capabilities and Device Type Mana
35PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.com2.7.2 MX/QX PB Device Installation VerificationVerify the
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12362.8.3 Checking the Normal DisplayPlace the selector switch in LOCAL
37PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comFigure 2.24b illustrates the PB DP field unit with a COMM
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1238Software3.1 PROFIBUS ProtocolThis fieldbus system uses the PROFIBUS fi
39PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comThe Transducer Block is used to convert signals from the
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/124FiguresFigure 1.1 – Typical PROFIBUS DP Network with DCS or PLC as the
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1240The following table provides generic descriptions of how the various
41PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comExecution of a function block, physical block or transduc
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1242Figure 3.3 – Analog Input BlockAnalog Input Function BlockEnableSimul
43PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comFigure 3.4 – Analog Input Block Scaling and FilteringFiel
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1244• LO_LIM, LO_LO_LIM, HI_LIM, and HI_HI_LIM – If the measured variabl
45PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comFigure 3.6 – Analog Output Function BlockDiscrete Input F
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1246POS_D (cyclic) is the current position of the valve (discrete):POS_D0
47PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comFigure 3.7 – Analog Output Block ScalingTemp = (SP – EU 0
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12483.5 Discrete Input (DI) Function BlockThe Discrete Input (DI) functi
49PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comThe FSAFE_VALUE_D (acyclic) parameter is the default valu
5PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.com1 Introduction1.1 PurposeThis manual explains how to insta
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12503.6 Discrete Output (DO) Function BlockThe Discrete Output (DO) bloc
51PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comFigure 3.11 – Discrete Output Function BlockDiscrete Outp
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1252CHECK_BACK_MASK is the definition of supported CHECKBACK information b
53PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comFigure 3.12 – MX/QX PROFIBUS Configuration RequirementsPRO
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1254 Associated Documents Additional information can be found in th
55PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.com5 How to Order Parts To order parts or obtain further i
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1256A Appendix – Wiring DiagramsPROFIBUS DPV1 Wiring Diagram CONTROL PAN
57PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comPROFIBUS DPV1 Wiring Diagram (con’t.)27CLOSESTOP26OPEN25D
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1258Redundant PROFIBUS DPV1 Wiring DiagramCONTROL PANELSENSORPOSITIONSENS
59PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comRedundant PROFIBUS DPV1 Wiring Diagram (con’t.)27CLOSESTO
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/126Appendix A – Wiring Diagram This section contains the detailed wiring
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1260PROFIBUS PA Wiring DiagramCONTROL PANELSENSORPOSITIONSENSORTORQUESENS
61PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.com11DWG NORAC 3/12/09R5114 WOODALL ROAD, LYNCHBURG, VIRGIN
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1262B Appendix – Feature DefinitionsTransducer Block I/O ChannelsThe foll
63PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comChannel 344 – Set Actuator Position (Index 104)This chann
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1264Channel 348DI_POSITION_CHAN ValueOpened 0x01Closed 0x02Opening 0x04Cl
65PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comChannel 350DI_ACTUATOR_FAULTS_2_CHAN ValueThermal Overloa
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1266Channel 351 – Actuator Alarms (Index 111)This channel, DI_ACTUATOR_AL
67PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comChannel 353 – Read Discrete Output (Index 113)This channe
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1268Channel 355 – Emergency Shutdown (Index 115)This channel, DO_ESD_CHAN
69PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comChannel 357 – Actuator Position Channel (Index 117)The v
7PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.com• Installation Guidelines for PROFIBUS – FMS/DP Version 1
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1270Status Bit DefinitionsReprinted from “PROFIBUS-PA Profile for Process C
71PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.com0 1 0 1 0 1 = engineering unit violation (unit not in th
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1272Invalid status valuesQuality Quality Substatus LimitsGr Gr QS QS QS Q
73PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.com1 0 0 0 1 0 1 0Good (Non-Cascade), active advisory alarm,
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1274Slot 1 – Analog Output Block There are eight possible module configura
75PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comStandard Parameters and ObjectsParameter DescriptionBlock
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1276Actuator Transducer Block Custom Parameter DescriptionsSome parameter
77PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comParameter Transducer Block DescriptionSCALED_VALUES(Index
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1278Parameter Transducer Block DescriptionTQ_STATUS(Index 99)Manufacturer
79PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comIdentification and Maintenance (I&M) FunctionsAs per “
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/128The devices used to create a segment are Repeaters for copper networks
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1280C Appendix – PROFIBUS Function Block Acyclic Parameter Descriptions
81PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comAnalog Output Function Block Specific Parameters (Slot 1)P
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1282Discrete Input Function Block Specific Parameters (Slots 2 through 5)P
83PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comParameter DescriptionINVERT(Index 34)Indicates whether th
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1284Parameter DescriptionPV_SCALE(Index 27)Conversion of the process vari
85PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comGlossaryTerm DescriptionCommunications Protocol A standa
PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/1286PROFIBUS is a data communication network which interconnects PROFIBUS
87PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comThis page intentionally left blank.
flowserve.comFlowserve Corporation has established industry leadership in the design and manufacture of its products. When properly selected, this Flow
9PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12flowserve.comPROFIBUS DP-V1InterfaceControl HighwayDistributed ControlS