Page 1 - TRV 5-40

1TRV 5-40Installation Instructions 818712-00Temperature Transmitter TRV 5-40GESTRA Steam SystemsGESTRA

Page 2 - Contents

10TRV 5-40Functional ElementsFig. 3E BDCFGAKJIHA Cross recess head screwsB Housing coverC Fixing lugs for wall mountingD Indication of limit setti

Page 3 - Contents – continued –

11WiringWiring of the temperature sensorNote that screened four-core cable, e. g. Ölflex® 110CH, Lapp, 4 x 0.5 mm2 is required for wiring the equipmen

Page 4 - Explanatory Notes

12Wiring – continued –Wiring diagram for temperature transmitter TRV 5-40Fig. 43 144512 253Key1 Screen2 Voltage supply 24 V DC+3 Voltage supply

Page 5

13Wiring – continued –Wiring diagram for temperature transmitter TRV 5-40 – continued –Attentionn Wire equipment in series. Start-type wiring is no

Page 6 - Technical Data

14Basic SettingsFactory settingsThe temperature transmitter TRV 5-40 features the following factory set default values:n Node ID: 005 for the safety

Page 7 - Technical Data – continued –

15Commissioning – continued –Examples of configuration settings1 ExampleThe following items of equipment are connected to the control unit NRS 1-40.1:

Page 8

16Commissioning – continued –Adjusting temp. limit TMAX (°C)NoteIn the parameter setting mode the currently adjusted value is indicated by both seven

Page 9 - Installation

17StartApply supply voltage. All segments and decimal points of the displays TMAX and T are flashing.The LED displays are being tested.OperationActual

Page 10

18CausesFaulty installation and/or configuration of CAN bus components, excessively high temperatures in devices, defective electronic component parts

Page 11 - UNITRONIC

19Systematic malfunction analysisThe sources of malfunctions occurring in CAN bus systems operating with several bus-based stations must be analysed s

Page 12 - 3 144512 253

2ContentsUsage for the intended purpose ...

Page 13

20Indication of error codeWhen an error occursIndication T Display switches between indication of error code (E xx) and actual value TError code Pos

Page 14 - Commissioning

21System Malfunctions – continued –NoteThe system malfunctions caused by the temperature transmitter TRV 5-40 will also result in system malfunctions

Page 15 - Commissioning – continued –

22MalfunctionsFault-finding list for TRV 5-40 / NRS 1-40.1 / NRS 1-40.2Switchpoint max. temp. limit (°C) not exceeded – max. temp. alarm raised.Fault:

Page 16

23AnnexCAN busAll devices (level, conductivity) are interconnected via CAN bus. The CANopen protocol is used for the data exchange between the equipme

Page 17 - Start, Operation and Test

24Node IDShould it be necessary to establish other node IDs please take the interdependence of the equipment into consideration and assign the node ID

Page 18 - System Malfunctions

25Annex – continued –Table “Node ID”In a CAN bus system a maximum of 123 nodes (devices) can be administered. Each node has its own address (node ID)

Page 19 - Check next system

26Declaration of Conformity We hereby declare that the equipment TRV 5-40 conforms to the following European guidelines:n LV guideline 73/23/EC versi

Page 21 - – continued –

28818712-00/1106cm · 2005 GESTRA AG · Bremen · Printed in GermanyGreat BritainFlowserve Flow Control (UK) Ltd.Burrel Road, Haywards HeathWest Sussex R

Page 23 - Control Units Sensors

4Important NotesUsage for the intended purposeThe temperature transmitter TRV 5-40 in conjunction with the temperature sensors TRG 5-63, TRG 5-64, TR

Page 24 - Annex – continued –

5Explanatory Notes – continued –Description – continued –The temperature transmitter TRV 5-40 can be used as:n safety temperature monitor / limiter

Page 25

6TRV 5-40Type approvalTÜV. SWB/SHWS. 03–413 EG BAF-MUC 03 07 103881 004 DIN registry no. STW (STB) 117 906Input/Output CAN bus interface with current

Page 26

7TRV 5-40 – continued –Housing Material: polycarbonateCable entry / Wiring For connecting the temperature sensor: Cable glands with integrated cable

Page 27 - For your notes

8Dimensions TRV 5-40Technical Data – continued –Fig. 2b = 60ABC180163.5168130

Page 28 - GESTRA AG

9InstallationCheck and if necessary change settings1. Undo cross recess head screws A and swing up the housing cover B.2. Use pushbuttons K for sett