1TRV 5-40Installation Instructions 818712-00Temperature Transmitter TRV 5-40GESTRA Steam SystemsGESTRA
10TRV 5-40Functional ElementsFig. 3E BDCFGAKJIHA Cross recess head screwsB Housing coverC Fixing lugs for wall mountingD Indication of limit setti
11WiringWiring of the temperature sensorNote that screened four-core cable, e. g. Ölflex® 110CH, Lapp, 4 x 0.5 mm2 is required for wiring the equipmen
12Wiring – continued –Wiring diagram for temperature transmitter TRV 5-40Fig. 43 144512 253Key1 Screen2 Voltage supply 24 V DC+3 Voltage supply
13Wiring – continued –Wiring diagram for temperature transmitter TRV 5-40 – continued –Attentionn Wire equipment in series. Start-type wiring is no
14Basic SettingsFactory settingsThe temperature transmitter TRV 5-40 features the following factory set default values:n Node ID: 005 for the safety
15Commissioning – continued –Examples of configuration settings1 ExampleThe following items of equipment are connected to the control unit NRS 1-40.1:
16Commissioning – continued –Adjusting temp. limit TMAX (°C)NoteIn the parameter setting mode the currently adjusted value is indicated by both seven
17StartApply supply voltage. All segments and decimal points of the displays TMAX and T are flashing.The LED displays are being tested.OperationActual
18CausesFaulty installation and/or configuration of CAN bus components, excessively high temperatures in devices, defective electronic component parts
19Systematic malfunction analysisThe sources of malfunctions occurring in CAN bus systems operating with several bus-based stations must be analysed s
2ContentsUsage for the intended purpose ...
20Indication of error codeWhen an error occursIndication T Display switches between indication of error code (E xx) and actual value TError code Pos
21System Malfunctions – continued –NoteThe system malfunctions caused by the temperature transmitter TRV 5-40 will also result in system malfunctions
22MalfunctionsFault-finding list for TRV 5-40 / NRS 1-40.1 / NRS 1-40.2Switchpoint max. temp. limit (°C) not exceeded – max. temp. alarm raised.Fault:
23AnnexCAN busAll devices (level, conductivity) are interconnected via CAN bus. The CANopen protocol is used for the data exchange between the equipme
24Node IDShould it be necessary to establish other node IDs please take the interdependence of the equipment into consideration and assign the node ID
25Annex – continued –Table “Node ID”In a CAN bus system a maximum of 123 nodes (devices) can be administered. Each node has its own address (node ID)
26Declaration of Conformity We hereby declare that the equipment TRV 5-40 conforms to the following European guidelines:n LV guideline 73/23/EC versi
27For your notes
28818712-00/1106cm · 2005 GESTRA AG · Bremen · Printed in GermanyGreat BritainFlowserve Flow Control (UK) Ltd.Burrel Road, Haywards HeathWest Sussex R
3TRV 5-40 ...
4Important NotesUsage for the intended purposeThe temperature transmitter TRV 5-40 in conjunction with the temperature sensors TRG 5-63, TRG 5-64, TR
5Explanatory Notes – continued –Description – continued –The temperature transmitter TRV 5-40 can be used as:n safety temperature monitor / limiter
6TRV 5-40Type approvalTÜV. SWB/SHWS. 03–413 EG BAF-MUC 03 07 103881 004 DIN registry no. STW (STB) 117 906Input/Output CAN bus interface with current
7TRV 5-40 – continued –Housing Material: polycarbonateCable entry / Wiring For connecting the temperature sensor: Cable glands with integrated cable
8Dimensions TRV 5-40Technical Data – continued –Fig. 2b = 60ABC180163.5168130
9InstallationCheck and if necessary change settings1. Undo cross recess head screws A and swing up the housing cover B.2. Use pushbuttons K for sett