Flowserve NRG 16-38S Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Matériel Flowserve NRG 16-38S. Flowserve NRG 16-38S User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer

Résumé du contenu

Page 1 - NRG 16-39S

1NRG 16-38SNRG 16-39SInstallation Instructions 810746-00Level Electrode NRG 16-38SLevel Electrode NRG 16-39S

Page 2 - Contents

10Explanatory Notes – continued –FunctionDesignsWater level limiter NRG 16-11The conductivity of the liquid is used to signal the liquid level. Some

Page 3 - Dimensions

11Technical DataType ApprovalGL 40 601-01 HHLR 01/20026ABS 01-HG 227959-PDABV 11400 / A1 BVDNV A-8394KR HMB 06190-MS 001NK A 557 / 02 A 013Service pre

Page 4

12Technical Data – continued –OutputsNRGT 26-1: Current output 4 – 20 mAlevel-proportional, volt-free, load 500 ohmResponse time of level changesNRG

Page 5 - Parts Drawings

13Corrosion ResistanceWhen used for its intended purpose the safe functionting of the equipment will not beimpaired by corrosion.Explanatory Notes –

Page 6

14Explanatory Notes – continued –Corrosion Resistance – continued –Designation of the equipmentFig. 8 NRG 16-11Designation of theequipmentFig. 9

Page 7

15Attention Handle electrode with care. Do not bend electrode tip when mountingand avoid subjecting the electrode to mechanical shocks. Do not lag e

Page 8 - Important Notes

16Installation – continued –Installing Terminal Box of Level Transmitter NRGT 26-1, step 31. Unscrew fixing nut of the electrode in the level tran

Page 9 - Explanatory Notes

17Note that screened four-core cable, e. g. I-Y(St)Y 2 x 2 x 0.8 or LIYCY 4 x 0.5 mm²is required for wiring the electrode.Max. cable length 100 m with

Page 10 - ■ NRG 16-39S

181. Use flexible cable to connect the power supply. Use a separate flexible screenedcable, min. conductor size 1.5 mm² for connecting the signal outp

Page 11 - – continued –

19Basic SettingsActive measuring range (control range)Max. measuring range at 25 °CWater, conductivity > 20 µS/cmWater, conductvity > 5 µS/cmFue

Page 12 - – continued –

2ContentsUsage for the intended purpose ...8Safety note ...

Page 13 - NRGT 26-1S

201. Fill boiler or vessel with liquid until the lower measuring point is reached.2. Raise the pressure in the steam boiler or tank until the service

Page 14 - NRG 16-38S, NRG 16-39S

21OperationDesigned for use in conjunction with controller NRS 1-7. Application in marine steamboilers and (pressurized) hot water installations in ac

Page 15 - Installation

22MalfunctionsIf faults occur that are not listed above, please contact our subsidiary or agency inyour country.WarningThe terminal strip of the NRGT

Page 16 - Installation – continued –

23Example of Installation12Fig. 1343KeyFlange PN 40, DN 100,DIN 2527 (NRG 16-38S)Flange PN 40, DN 150,DIN 2527 (NRG 16-39S)For the approval of the boi

Page 17

24810746-00/303cs · © 2002 GESTRA GmbH · Bremen · Printed in GermanyGESTRA Gesellschaften · GESTRA Companies · Sociétés GESTRA · Sociedades Gestra ·

Page 18 - Wiring – continued –

3DimensionsFig. 1 NRG 16-38SNRGT 26-1NRG 16-113004005006007008009001000110012001300140015002000358462 5686737798849891095119913041408151316212141NR

Page 19 - Basic Settings

4DimensionsFig. 2 NRG 16-39S1

Page 20 - Commissioning

5Parts DrawingsFig. 3BCDEFFig. 4AU

Page 21 - Operation

6Parts DrawingsFig. 5MAX 70°CMAX 95%Fig. 6POG HIHQL NJMKRST

Page 22 - Malfunctions

7KeyBCDFGHIEKJLNMOAPQRSTUMeasuring electrodeBoreSpringElectrode tipPTFE insulating tubeSTARLOCK® retaining ringHousing screws M4Cable gland M 16 (PG 9

Page 23 - Example of Installation

8Important NotesSafety NoteDangerWhen loosening the electrode steam or hot water might escape.This presents the danger of severe injuries to the whole

Page 24 - GESTRA GmbH

9Explanatory NotesScope of SupplyNRG 16-38S1 Level electrode type NRG 16-38 S1 Terminal box for level transmitter1 Installation manualNRG 16-39S1 Leve