NRS 1-50
For ONE Electrode
Installation Instructions 818987-00
Level Switch NRS 1-50
GESTRA Steam Systems
GESTRA
EN
English
Vue de la page 0
1 2 3 4 5 6 ... 23 24

Résumé du contenu

Page 1 - NRS 1-50

1NRS 1-50 For ONE ElectrodeInstallation Instructions 818987-00Level Switch NRS 1-50GESTRA Steam SystemsGESTRA ENEnglish

Page 2 - Contents

10Name plate / markingFig. 5Type designationMains voltage/ ProtectionSerial numberManufac-turerWiring diagramSafety noteDisposal noteTechnical Data

Page 3 - Contents - continued

111 2 3 4 5 6 7 8 9 10 11 12 13 14 15122716 17 18 19 20 21 22 23 24 25 26 28 29 30Fig. 6Dimensions and Functional ElementsNRS 1-50123451 Upper termin

Page 4 - Application

12Safety noteThis device is an item of equipment with safety function (PED) and must only be installed, wired and commissioned by qualified and compete

Page 5 - Directives and Standards

13Electrical ConnectionConnection of level electrodeTo connect the level electrode use screened multi-core control cable with a min. conductor size 0

Page 6

14Electrical Connection - continued -Toolsn Screwdriver for slotted screws, size 3.5 x 100 mm, completely insulated according to VDE 0680-1.Dangern

Page 7

1527161 2 3 4 5 6 7 817 18 19 20 21 22 23 24925102611 12281329143015NRG 1...-50NRG 16-36LM 0,5A(+)+(-)-NN NL L1212433Electrical Connection - continue

Page 8 - Technical Data

16defFig. 8defFig. 9Electrical Connection - continued -Schematic representations of arrangementsddgeffFig. 10 Fig. 11eed Level electrode NRG 1...-50

Page 9

17Electrical Connection - continued -Explanatory notes to schematic respresentationsSteam boiler plants and (pressurized) hot-water installations ac

Page 10 - NRS 1 - 50

18Commissioning ProcedureDangerThe terminal strips of the equipment are live during operation.This presents the danger of electric shock!Always cut of

Page 11

19Commissioning - continued - Checking switchpoint and functionStartActivity Indication FunctionApply mains voltage. All LEDs are illuminated.System

Page 12 - Important Notes

2ContentsUsage for the intended purpose ...

Page 13 - Installation

20OperationActivity Indication FunctionLevel electrode submerged.Green LED for level electrode 1 is illuminatedOutput contacts are closed. Signal ou

Page 14 - - continued

21Troubleshooting - continued -Diagnosis Display 1 and activity Display 2 Fault Remedy LED alarm 1 and diagnosis LED 1 illuminated. Press and hold d

Page 15

22Measure the electrode voltage in order to check whether the level electrode is immersed or if there is a malfunction. Please observe Fig. 15. ≈ 0.7

Page 16 - Fig. 10 Fig. 11

23Action against high frequency interferenceShould sporadic failures occur in installations susceptible to faults (e. g. malfunctions due to out-of-ph

Page 17

24818987-00/12-2009cm (808835-00) · GESTRA AG · Bremen · Printed in GermanyAgencies all over the world:www.gestra.deGESTRA AGP. O. Box 10 54 60, D-28

Page 18 - Basic Settings

3Contents - continued -Checking switchpoint and function ...

Page 19 - Commissioning - continued

4ApplicationUsage for the intended purposeThe level switch NRS 1-50 is used in conjunction with level electrode NRG 1...-.. to limit the water level i

Page 20 - Troubleshooting

5Directives and StandardsPressure Equipment Directive (PED) 97/23/ECWater level limiters are safety accessories as defined in the Pressure Equipment Di

Page 21

6Functional Safety acc. to IEC 61508Safety characteristics of the subsystem NRG 1...-50 / NRS 1-50The level switch NRS 1-50 is certified acc. to IEC 61

Page 22 - Malfunction (immersed/alarm)

7Functional safety acc. to IEC 61508 - continued -Determination of the Safety Integrity Level (SIL) for safety-related systemsLevel electrode, level

Page 23 - Further Notes

8NRS 1-50Supply:Mains voltage 24 VDC +/– 20 %, 0.3 A or 100 – 240 VAC +10/–15 %, 47 – 63 Hz, 0.2 AExternal fuse 0.5 A (semi-delay)Power consumption 7

Page 24 - GESTRA AG

9NRS 1-50 - continued -Further conditions: Ambient temperature when system is switched on: 0 ° ... 55 °C during operation: -10 ... 55 °CTransport te