Tools
Screwdriver for slotted screws, size 2.5, completely insulated according to
VDE 0680
Wiring – continued –
Note
Connect screen only to terminal 3, ensuring electrical continuity and
connect equipment once to the central earthing point (CEP).
The loop resistance must be under 10 .
The rated voltage is stated on the name plate.
Despite correct wiring H.F. interference caused by the installation may
lead to system breakdowns and malfunction messages. If necessary
refer to the fault finding lists of the respective bus equipment.