
AXENIM0048-01 (Firmware Rev. Nov. 12 99) (AUTO-48) 11/01 Page 3 of 16
©2001, Flowserve Corporation, Springville, UT
Flowserve Corporation 1350 South Mountain Springs Parkway Phone: 801 489 2233
Flow Control Division Springville, Utah 84663 Facsimile: 801 489 2228
Automax Valve Automation Systems
Product Specification
Printed Circuit Board Specifications
Power Requirements: Communications Card
XA0239
Communications Card
Bus powered
9.5-32 VDC at 14 mA
Power requirements: 2-Wire Version
XA0338 Interface Card
Version 2.0
Bus-Powered by XA0239
Communication Card
Power requirements
†
: 4-Wire Version
XA0242 Interface Card 24 VDC
x 10 mA quiescent
x 510 mA max. with
solenoid activated.
Temperature
Operational -40 °F to +185 °F
(-40 °C to +85 °C)
Storage -40 °F to +250 °F
(-40 °C to +120 °C)
† To operate, an external 24 VDC source must be locally
supplied to the interface card.
Intrinsically Safe Entity Parameters
(FR-Series BUSwitch only)
Class 1, Div. 1, Groups A-G & ATEX EEx ia IIC T4
V max = 24V, I max = 250mA
Ci = 5 nF, Li = 8 µH
FOUNDATION£ Fieldbus Information
Manufacturer
ID 0x46 4C4F (Hex)
Name 46 6C 6F 77 73 65 72 76 65
F l o w s e r v e
Device
Type 0x50 53 (Hex)
ID 464 C4F5053:BUSWITCH:xxxxxx
Max length of 32 characters. Characters
21 through 32 are used for board serial
number.
Device Descriptions are supplied on included diskette
or can be downloaded from the Fieldbus Foundation
website (www.fieldbus.org).
Start-up Guide
1. Following the instructions in “Mechanical Installation,”
install the BUSwitch™ onto a pneumatic actuator and
turn supply air on.
2. Following the instructions in “Electrical connections,”
connect fieldbus and optional dry-contact wiring.
3. Referring to control system or configuration system
documentation, install BUSwitch™ device description
(DD) files onto system hard drive. Note: Readme file
on DD floppy contains instructions.
4. Initialize communications with device and bring up the
“Live List.” BUSwitches have been
configured from
the factory with an ID of “464C4F5053:BUSWITCH:
[serialnumber]” and a default tag of “FLOWSERVE
BUSWITCH.” Note the serial number.
5. Change the BUSwitch™ attribute Device ID to the
value noted in step 4 and change the Device Tag to
the appropriate value.
6. Assign the Tag configuration in step 5.
7. BUSwitches are shipped with resource block,
transducer block, (2) DO blocks and (4) DI blocks pre-
configured unless specially configured by agreement
with customer. Refer to the appropriate sections in
this manual for the default configuration. Make any
desired changes to this configuration and download.
CAUTION
The BUSwitch may cycle during a configuration
download. Exercise caution in handling valves
that may be stroked during these procedures.
For best results, Flowserve strongly
recommends reading this entire document
before attempting to configure and commission
BUSwitches.
Note: For Fisher DeltaV systems, the DD files
must be copied to a directory or folder named
“
”
in order for the system to find them.
Commentaires sur ces manuels