Flowserve MX FOUNDATION Fieldbus Field Unit Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Matériel Flowserve MX FOUNDATION Fieldbus Field Unit. Flowserve MX FOUNDATION Fieldbus Field Unit User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer

Résumé du contenu

Page 1 - USER INSTRUCTIONS

Experience In MotionUSER INSTRUCTIONSInstallationOperationMaintenanceMX/QX FOUNDATION Fieldbus Field UnitFCD LMENIM2330-01 – 08/11

Page 2 - Contents

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1110Figure 2.2 - QX-05 Actuator2.2.1 MX/QX Electric Actuators The MX/QX actuators control

Page 3

11MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.com2.2.2 MX/QX FF Interface Board The MX/QX FF field unit interface board is

Page 4 - Introduction

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1112Figure 2.3 – MX/QX Interface Board2.2.3 Network Host The FOUNDATION fieldbus network i

Page 5 - 1.4 User Knowledge

13MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comUnscheduled Communication All devices on the fieldbus are given a chance t

Page 6

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1114The following Figure 2.4 illustrates these four types of network. Details such as pow

Page 7

15MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comPower Conditioners are power supply impedance matching networks and are r

Page 8

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1116Figure 2.6 – Fieldbus Power Supply with External TerminationFigure 2.7 – Fieldbus Pow

Page 9 - System Components

17MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.com2. Prepare the cable and label all wires. See Section 2.6.2. 3. Install

Page 10

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1118NOTE: • Shielded twisted-pair cables are used. • Shields are connected to earth gro

Page 11 - flowserve.com

19MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.com3. Cut away the foil shield. Strip the insulation from the conductors ap

Page 12 - 2.2.3 Network Host

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/112Contents1 Introduction 41.1 Purpose 41.2 How to Use this Manual 41.3 User Safet

Page 13 - 2.2.4 Network Cable

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11206. Connect the network cables to the MX/QX terminal block as shown in Figure 2.14. T

Page 14 - 2.3 Other Network Components

21MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.com2.6.2.2 Network Cable Connections to Other Network Components Each FOUNDA

Page 15 - 2.5 Fieldbus Power Supply

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1122The maximum length of the fieldbus cable is determined by the following: • Communicat

Page 16 - 2.6.1 Site Preparation

23MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comFigure 2.16 – MX/QX FF Setup SequenceNOTE: This menu is displayed after t

Page 17

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11246. OPEN/CLOSE or POSITION display allows selection of the mode of operation of the

Page 18

25MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.com2.8 Installation Verification 2.8.1 Network Cabling Installation Verificati

Page 19

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11262.9.2 View Settings Refer to Installation and Operation Manual Bulletins LMENIM2306,

Page 20

27MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.com3 Software 3.1 Fieldbus Protocol The fieldbus system uses the FOUNDATION fi

Page 21

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1128Figure 3.1 – Fieldbus Function BlocksA Virtual Field Device (VFD) is used to remotely

Page 22 - 2.6.4 MX/QX FF Device Setup

29MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.commeasurement. The measuring device may have several measurements or derive

Page 23

3MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comContents4 Associated Documents 405 How to Order Parts 41A Appendi

Page 24 - 2.6.5 Valve Data

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1130Filter The PV filter, whose time constant is PV_FTIME, is applied to the PV, and not t

Page 25 - 2.9 Configuration Confirmation

31MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comRCAS_IN is a target setpoint and status provided by a supervisory host to

Page 26 - 2.9.2 View Settings

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1132Chan. No.4 — DI_ACTUATOR_FAULTS_1_CHAN — Mechanical and electrical faults 1 Chan.

Page 27 - Software

33MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comThis feature requires the installation of a hardware jumper on the MX/QX

Page 28 - Actuator

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1134RCAS_OUT_D is a block setpoint and status provided to a supervisory host for back cal

Page 29

35MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comFigure 3.6 – Proportional Integral Derivative Function BlockSetpoint sele

Page 30 - Analog Output Block

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1136The TRK_VAL parameter specifies the value to be converted and tracked into the output

Page 31

37MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comAlarm DetectionA block alarm will be generated whenever the BLOCK_ERR has

Page 32 - Discrete Input Block

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11383.8 Transducer Block The custom transducer block is the interface between the functio

Page 33

39MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comTable 3.2 – Summary of Device Descriptions and Capabilities Files Device

Page 34 - Function Block

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1141 Introduction 1.1 Purpose This manual explains how to install and operate the MX/QX F

Page 35

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11404 Associated Documents Additional information can be found in the following document

Page 36

41MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.com5 How to Order Parts To order parts or obtain further information about y

Page 37

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1142A Appendix A – Wiring Diagrams Figure A.1 (1 of 3) – Typical MX/QX FF_H1 Wiring Diag

Page 38 - 3.8 Transducer Block

43MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comFigure A.2 (2 of 3) – Typical MX/QX FF_H1 Wiring Diagrams (continued)

Page 39

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1144Figure A.3 (3 of 3) – Typical MX/QX FF_H1 Wiring Diagram Notes

Page 40 - Documents

45MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comB Appendix – Feature Definitions Transducer Block I/O Channels The follow

Page 41 - How to Order Parts

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1146Channel 2 – Position and Bus Mode The channel 2 Discrete Input function block, DI_POS

Page 42 - Diagrams

47MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comChannel 4 DI_ACTUATOR_FAULTS_1_CHAN ValueMonitor Relay 0x01Valve Jammed 0

Page 43

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1148Channel 6 – Actuator Alarms The Channel 6 Discrete Input function block, DI_ACTUATOR_

Page 44

49MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comChannel 8 – Read Discrete Output The Channel 8 Discrete Input function bl

Page 45 - Definitions

5MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.com1.3 User Safety Safety notices in this manual detail precautions the user

Page 46 - Channel 3 – Position Channel

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1150Channel 10 – Emergency Shutdown The Channel 10 Discrete Output, DO_ESD_CHAN, accepts

Page 47

51MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comTransducer Block Parameters DescriptionST_REV The revision level of the s

Page 48 - Channel 6 – Actuator Alarms

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1152Transducer Block Parameters DescriptionXD_ERROR One of the transducer error codes defi

Page 49 - Channel 9 - Position

53MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comTransducer Block Parameters DescriptionVALVE_TYPE The type of the valve a

Page 50 - Custom Transducer Block (LTB)

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1154Transducer Block Parameters DescriptionBit 04 Closing – Valve is traveling in the Clo

Page 51

55MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comTransducer Block Parameters DescriptionBit 04 Closing – Valve is travelin

Page 52

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1156Transducer Block Parameters DescriptionBit 04 User Output R3 (optional) – Indicates t

Page 53

57MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comTransducer Block Parameters DescriptionBit 07 Not Used Bit 08 User Input

Page 54

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1158Transducer Block Parameters DescriptionBit 09 PB PA Board PresentBit 10 CSE Chosen fo

Page 55

59MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comTransducer Block Parameters DescriptionSubparameter 0 uint16_varUnusedSub

Page 56

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1161.5 MX/QX FF System Capabilities and Features Limitorque’s FOUNDATION fieldbus field uni

Page 57

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1160Transducer Block Parameters DescriptionBit 11 Over torqueBit 12 Phase sequence warnin

Page 58

61MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comTransducer Block Parameters DescriptionBit 09 Pair # 109 (D109/Q109) of w

Page 59

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1162Transducer Block Parameters DescriptionBit 13 Pair # 13 (D13/Q13) of wheel 4 faultBit

Page 60

63MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comTransducer Block Parameters DescriptionBit 12 CW not asserted but relay d

Page 61 - Subparameter 1

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1164Transducer Block Parameters DescriptionSubparameter POSITIONPredetermined user-configu

Page 62 - SOURCE_OF_LIMIGARD

65MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comTransducer Block Parameters DescriptionDTM_OPERATIONDTM operation can be

Page 63

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1166Transducer Block Parameters DescriptionSubparameter POLARITYAnalog-1 output polarity

Page 64

67MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comTransducer Block Parameters DescriptionSubparameter R3_FUNCTIONFunction a

Page 65

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1168Transducer Block Parameters DescriptionSubparameter R7_FUNCTIONFunction assigned to t

Page 66

69MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comTransducer Block Parameters DescriptionSubparameter MANUAL_OPERATIONSTota

Page 67

7MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comFigure 1.1 – Typical FOUNDATION Fieldbus System with a DCS HostPower for t

Page 68

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1170C Appendix – Fieldbus Parameter DescriptionsFOUNDATION Fieldbus employs the followin

Page 69

71MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comBKCAL_OUT The value and status required by an upper block’s BKCAL_IN so t

Page 70 - Descriptions

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1172COLLECTION_DIRECTORY A directory that specifies the number, starting indices, and DD I

Page 71

73MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comDV_LO_PRI Priority of the low deviation alarm. FAULT_STATE Condition set

Page 72

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1174HARD_TYPES The types of hardware available as channel numbers. HI_ALM The status for

Page 73

75MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comLO_LO_PRI Priority of the low low alarm. LO_PRI Priority of the low alarm

Page 74

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1176PV_D Either the primary discrete value for use in executing the function, or a proces

Page 75

77MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comRS_STATE State of the function block application state machine. SEL_1 Fir

Page 76

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1178SP_RATE_UP Ramp rate at which upward setpoint changes are acted on in Auto mode, in P

Page 77

79MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comXD_SCALE The high and low scale values, engineering units code, and numbe

Page 78

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1181.5.1 General Network Specification System Specifications: • Communicates using the FOU

Page 79

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1180GlossaryCommunications Protocol A standard for transferring data between intelligent

Page 80 - Glossary

81MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comProportional Integral Derivative Control Methodology Control loop feedba

Page 81

MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/1182This page intentionally left blank.

Page 82

83MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.comThis page intentionally left blank.

Page 83

flowserve.comTo find your local Flowserve representative, visit www.flowserve.com, www.limitorque.com or call USA 1 800 225 6989Flowserve Corporation

Page 84

9MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11flowserve.com2 System Components and Installation 2.1 Introduction This section is an