Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
flowserve.com
1.5 Product Specifications
Table 1.1 – Modutronic 20 II Specifications
Power Requirements Derived from actuator supply
Board power 18 VAC or 24 VDC (±10%).3 VA
Control Signal 4-20 mA
Accuracy Within ±1% (>30 second stroke)
Loss of Command Signal Selections
Fail-to-last-position
Fail-to-minimum-signal-position
Temperature -40°C to +85°C (operating)
Maximum Starts Solid state reverser–600/hour
Per Hour Electromagnetic contactor–100/hour
Maximum Direct Output Loading Motor current–4.5 A Inrush, 3 A Holding
Dimensions Mod 20–1.5”H x 3.25”W x 4”L
Separate enclosure
11.7”H x 12.75”W x 17.4”L
Deadband Adjustable between 1% and 10%
Resolution 1%
Linearity 1%
Humidity To 95% (non-condensing)