Menus of Inputs/Outputs – continued –
LRG 16-40 setup
1. In the menu LRG 16-40 CAN 1...10 press .
2. To establish or change the node ID
click in the green input field.
3. Use the on-screen keyboard to overwrite
or modify the value in the input mask.
4. Use button Node On/Off to activate or de-
activate the node ID.
5. To name the LRG 16-40 click in the input
field Name.
6. Use the on-screen keyboard to overwrite
or modify the value in the input mask.
7. To change the values of the LRG 16-40 click in the input field. First establish the
0% -100% range and then enter further values.
8. Use the on-screen keyboard to overwrite or modify the value in the input mask.
9. Use to delete the adjusted equipment or to change the type of equipment.
LRG 16-40
Setup
Logo
0
Name
Node Off
Node ID
0 µS
0 µS
0 µS
0 µS
Node On
Range 100%
Range 0%
0.00
0.00
Delete
electrode?
Note
The HiHi and LoLo settings can be used for alarms and the Hi and Lo settings
for switchpoints of 2-position controllers.
For the 72 hrs operation according to TRD 604 the switchpoint HiHi does not
replace the independent equipment in the safety chain
The alarm monitoring function is de-activated when all HiHi to LoLo values
have been set to 0 µS.
The node ID settings of SPECTORcontrol must agree with the settings of the
respective devices.